Reading Ex / ATEX Markings

Zones, gas groups and temperature classes for actuator accessories in hazardous areas.

Updated

  • ATEX
  • IECEx
  • zones
  • T-class

Solenoids, switchboxes and positioners on automated valves often sit in hazardous areas. The Ex marking tells you where they can be used.

Zone (gas)Explosive atmosphere present
Zone 0Continuously or for long periods
Zone 1Likely in normal operation
Zone 2Not likely, and only briefly if it does
T-classMax component temp during operation (°C)
T1450
T2300
T3200
T4135
T5100
T685

Gas groups run IIA (e.g. propane), IIB (e.g. ethylene) to IIC (hydrogen, acetylene). Equipment rated IIC is suitable for IIB and IIA; the reverse is not true.