Skip to content
Vectis Controls

Reading Spring-Return Torque Curves

Air stroke vs spring stroke, and why a stronger spring is not always the safer choice.

Updated

  • spring return
  • fail safe
  • FC
  • FO

A spring-return actuator has two separate output curves: the air (or hydraulic) stroke, which compresses the spring, and the spring stroke, which drives the valve to its fail-safe position.

The trade-off

  • Spring torque falls as the spring extends, spring end is the weakest point.
  • Air stroke output is reduced by the spring it is compressing, air end is the weakest point.
  • A stronger spring raises spring-end torque but lowers air-end torque at the same supply pressure.

For a fail-close (FC) valve the spring stroke must satisfy the close torques (BTC, RTC, ETC); for fail-open (FO) the spring satisfies the open torques. The air stroke handles the opposite direction. The same actuator body and spring set is simply mounted to produce the required fail action.

See also Sizing a Quarter-Turn Actuator to a Valve and Designing for Ultra-Fast Stroke Times.